Power system control and stability
1 Solving the Swing Equation for a network of 3 generators
during a fault and post fault
i = 1, 2, 3 | (1) |
---|
given by: | 2Hi | (2 | |
---|---|---|---|
ωi |
|
(2 | |
|
(3) |
2
3. what is the largest number of cycles before the fault must be cleared for the network to be stable post fault ?
units for power and admittance matrices below are in pu based on a 100 MVA base. The excitation voltages for the generators in pu are: Ei = 1.0566, 1.0502, 1.0170 and the initial angle of generator 1 is δ1 = 2.2717◦respectively. Network admittance matrices:
4 | Yprefault = | | 0.846 − j2.988 0.287 + j1.513 |
|
(4) | |||||
---|---|---|---|---|---|---|---|---|---|---|
0.210 + j1.226 | ||||||||||
Yfault = | | 0.657 − j3.816 0.000 + j0.000 |
|
|
(5) | |||||
|
||||||||||
0.070 + j0.631 | ||||||||||
Ypostfault = | | 1.181 − j2.229 0.138 + j0.726 | (6) | |||||||
0.191 + j1.079 | ||||||||||
|
Anderson, P.M. and Fouad, A.A Power System Control and Stability, IEEE-Wiley Press book, 2003, Pgs. 35 - 47. Note: This book can be accessed online through the library using the IEEE Database.